TW 600V

Covered Copper - TW 600V
Underwrites Laboratories logo

Product Description

Annealed solid or stranded uncoated copper conductor insulated with PVC, providing an abrasion, flame retardant, moisture and oil resistant insulation. Conductor is surface printed.

Colors available upon request.

Application

General purpose wiring for residential, commercial, and industrial lighting and power application as specified by the National Electric Code (NEC). Suitable for use in wet or dry locations where maximum continuous conductor temperatures do not exceed 60˚ C and for circuits not exceeding 600 volts.

Specification Data

Underwriters Laboratories Standard 83 for Thermoplastic Insulated Wires

Federal Specification J-C-30

National Electric Code Article 130

ASTM B-3 Soft or annealed copper wire
ASTM B-8 Concentric lay stranded copperconductors

Product Data

Solid

Size (AWG) Stranding Insulation Thickness (Mils) Nominal Diameter (inches) Weight Per 1000 Ft. (lbs.) Ampacity* 3 Cond. In Conduit Ampacity* 1 Cond. In Free Air
14 SOLID 30 0.125 18 15 20
12 SOLID 30 0.145 26 20 25
10 SOLID 30 0.165 40 30 40
8 SOLID 45 0.2185 64.5 40 60
6 SOLID 60 0.2820 108.0 55 80

Stranded

Size (AWG) Stranding Insulation Thickness (mils.) Nominal Diameter (inches) Weight Per 1000 Ft. (lbs.) Ampacity* 3 Cond. In Conduit Ampacity* 1 Cond. In Free Air
10 7 30 0.176 42 30 40
8 7 45 0.236 68 40 60
6 7 60 0.305 110 55 80
4 7 60 0.352 162 70 105
2 7 60 0.41 245 95 140

+Per NEC Table 310-16

*Manufactured with pride in DeKalb, IL USA.