Aluminum Use-2

Covered Aluminum - Aluminum USE-2
Underwrites Laboratories logo

Product Description

Annealed, solid or stranded aluminum alloy (EC1350) conductor, insulated with an abrasion, moisture, and heat resistant cross-linked (XLP) polyethylene.

Application

Type USE2 or RHW2 or RHH2 conductors are used in air, conduit or other approved raceways as specified in the national electrical code. USE2 or RHW2 or RHH2 can be used as underground service entrance cable, for direct burial at temperatures not to exceed 75°C; or when used as RHW2 conductor, temperatures are not to exceed 75°C in wet locations; or when used as RHH2 in dry locations, conductor temperatures are not to exceed 90°C. 250 MCM and larger sizes may be installed in tray per NEC Article 318. Conductor is rated 600 volts.

Specification Data

Underwriters laboratories standard 44 (RHW or RHH)
Underwriters laboratories standard 854 (USE)
Federal Specification J-C-30
National Electric Code

Product Data

ConductorInsulation Thickness (mils.)Complete Cable Diameter (inches)Allowable Ampacities+Approx. Net Weight Per 1000' (lbs.)
Size (AWG or kcmil)Stranding75°C90°C
8760.266404537
6760.304404550
4760.352657568
2760.4129010096
11980.492100115130
1/01980.533120135155
2/01980.579135150190
3/01980.630155175230
4/01980.688180205275
2503795.765205230320
3003795.820230255375
3503795.871250280440
4003795.918270305495
50037951.003310350605
600611101.113340385715
750611101.218385435885
1000611101.3724455001145

*Manufactured with pride in DeKalb, IL USA.