AAC, ACSR, and AAAC Service Drop Quadruplex

Product Description

Three stranded all aluminum conductors covered with HMW or cross-linked (XLP) polyethylene twisted around a bare ACSR conductor.

Application

Used in the overhead transmission of power from pole to building weatherhead.

Specification Data

ASTM B-230 Aluminum 1350-H19 wire for electrical purposes
ASTM B-231 Concentric-lay-stranded aluminum 1350 conductors
ASTM B-232 Concentric-lay-stranded aluminum conductors, coated-steel reinforced (ACSR)
ASTM D-1248 Polyethylene plastics molding and extrusion materials
ANSI C-8.35 Specifications for weather-resistant polyethylene-covered wire and cable
ICEA S-61-402
NEMA PUB NO. WC 5 Standards publication thermoplastic insulated wire and cable for the transmission and distribution of electrical energy

Product Data

AAC Neutral-Messenger

Code Word Phase Conductor Bare Neutral Messenger Weight Per 1000 ft. (lbs.) Allowable Ampacities+
Size (AWG) Stranding Covering Thickness (mils.) Size (AWG) Stranding Rated Strength (lbs.) POLY XLP POLY XLP
Clydesdale 4 1 45 4 7 881 198 199 80 100
Pinto 4 7 45 4 7 881 211 218 80 100
Mustang 2 7 45 2 7 1350 312 318 105 135
Criollo 1/0 19 60 1/0 7 1990 505 520 140 180
Percheron 2/0 19 60 2/0 7 2510 622 639 160 205
Hanovarian 3/0 19 60 3/0 19 3310 750 761 185 235
Oldenburg 4/0 19 60 4/0 19 4020 928 941 210 275

ACSR Neutral-Messenger

Code Word Phase Conductor Bare Neutral Messenger Weight Per 1000 ft. (lbs.) Allowable Ampacities+
Size (AWG) Stranding Covering Thickness (mils.) Size (AWG) Stranding Rated Strength (lbs.) POLY XLP POLY XLP
Morochuca 6 1 45 6 6/1 1190 145 147 60 75
Chola 6 7 45 6 6/1 1190 153 158 60 75
Morgan 4 1 45 4 6/1 1860 217 219 80 100
Hackney 4 7 45 4 6/1 1860 229 236 80 100
Palomino 2 7 45 2 6/1 2850 346 355 105 135
Standardbred 1/0 7 60 1/0 6/1 4380 557 573
Costena 1/0 19 60 1/0 6/1 4380 551 566 140 180
Grullo 2/0 19 60 2/0 6/1 5310 680 697 160 205
Suffolk 3/0 19 60 3/0 6/1 6620 824 835 185 235
Appaloosa 4/0 19 60 4/0 6/1 8350 1042 1063 210 275

6201 Alloy Neutral Messenger

Code Word Phase Conductor Bare Neutral Messenger Weight Per 1000 ft. (lbs.) Allowable Ampacities+
Size (AWG) Stranding Covering Thickness (mils.) ACSR Equivalent (AWG) Stranding Rated Strength (lbs.) POLY XLP POLY XLP
Bay 6 1 45 6 7 1110 137 137 60 75
French Coach 6 7 45 6 7 110 146 146 60 75
German Coach 4 1 45 4 7 1760 205 205 80 100
Arabian 4 7 45 4 7 1760 217 217 80 100
Belgian 2 7 45 2 7 2800 328 328 105 135
Shetland 1/0 19 60 1/0 7 4460 519 519 140 180
Thoroughbred 2/0 19 60 2/0 7 5390 639 639 160 205
Trotter 3/0 19 60 3/0 7 6790 789 789 185 235
Walking 4/0 19 60 4/0 7 8560 977 977 210 275

+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.
*Manufactured with pride in DeKalb, IL USA.

PDF versionPDF version