600V Underground Distribution Cable

Product Description

Duplex, Triplex or Quadriplex assembled, hard drawn 1350 aluminum conductors. Black cross-linked (XLP) polyethylene insulation on phase conductors and sold yellow (XLP) insulation on the neutral conductor for identification.

Application

Designed for secondary distribution and underground service at 600 volts or less.

Specification Data

Aluminum is an AAC. With ICEA S-66-524, Park 3 Part. 3.6. 1350 Aluminum conductor XLP insulation 90°C

ASTM B-230
ASTM B-231

Product Data

Duplex Solid Yellow Neutral

Code Word Phase Conductor Neutral Diameter (mils.) Weight Per 1000 feet (lbs.) Allowable Ampacities+
Size (AWG) Stranding Insulation Thickness (mils.) Size (AWG) Stranding Insulation Thickness (mils.) Single Phase Cond. Complete Cable Direct Burial In Ducts
Clafin 6 7 60 6 7 60 298 596 91 95 70
Delgado 4 7 60 4 7 60 345 690 129 125 90

+For NEC Applications, use NEC Table 310.16 Ampacities.

Triplex Solid Yellow Neutral

Code Word Phase Conductor Neutral Diameter (mils.) Weight Per 1000 feet (lbs.) Allowable Ampacities+
Size (AWG) Stranding Insulation Thickness (mils.) Size (AWG) Stranding Insulation Thickness (mils.) Single Phase Cond. Complete Cable Direct Burial In Ducts
Erskine 6 7 60 6 7 60 298 644 136 95 70
Vassar 4 7 60 4 7 60 345 745 194 125 90
Stephens 2 7 60 4 7 60 403 870 260 165 120
Ramapo 2 7 60 2 7 60 403 870 290 165 120
Brenau 1/0 19 80 2 7 60 512 1106 409 215 160
Bergen 1/0 19 80 1/0 19 80 512 1106 476 215 160
Converse 2/0 19 80 1 19 80 555 1199 490 245 180
Hunter 2/0 19 80 2/0 19 80 555 1199 540 245 180
Hollins 3/0 19 80 1/0 19 80 603 1302 586 280 205
Rockland 3/0 19 80 3/0 19 80 603 1302 656 280 205
Sweetbriar 4/0 19 80 2/0 19 80 658 1421 740 315 240
Monmouth 4/0 19 80 4/0 19 80 658 1421 847 315 240
Pratt 250 37 95 3/0 19 80 732 1581 857 345 265
Wesleyan 350 37 95 4/0 19 80 831 1795 1135 415 320
Rider 500 37 95 350 37 95 980 2117 1248 495 395

Quadriplex Solid Yellow Neutral

Code Word Phase Conductor Neutral Diameter (mils.) Weight Per 1000 feet (lbs.) Allowable Ampacities+
Size (AWG) Stranding Insulation Thickness (mils.) Size (AWG) Stranding Insulation Thickness (mils.) Single Phase Cond. Complete Cable Direct Burial In Ducts
Tulsa 4 7 60 4 7 60 345 833 258 120 85
Dyke 2 7 60 4 7 60 403 973 367 155 115
Wittenberg 2 7 60 2 7 60 403 973 375 155 115
Notre Dame 1/0 19 80 2 7 60 512 1236 574 200 150
Purdue 1/0 19 80 1/0 19 80 512 1236 596 200 150
Syracuse 2/0 19 80 1 19 80 555 1340 664 225 170
Lafayette 2/0 19 80 2/0 19 80 555 1340 720 225 170
Swarthmore 3/0 19 80 1/0 19 80 603 1456 805 250 195
Davidson 3/0 19 80 3/0 19 80 603 1456 874 250 195
Wake Forest 4/0 19 80 2/0 19 80 658 1588 1036 290 225
Earlham 4/0 19 80 4/0 19 80 658 1588 1066 290 225

+Ampacity: 90°C conductor temperature, 20°C ambient, RHO 90, 100% load factor for three conductor triplex with neutral carrying on unbalanced load.